Integrated Area Monitor
  • Long-life semiconductor sensor
  • Integrated visual and audible alarms
  • Affordable detection of VRF/VRV refrigerants
  • Remote sensor with aesthetic faceplate for discreet monitoring
  • Two on-board relays activate shut-off valves or fans

 

The IAM-100 area monitor is specifically designed to provide continuous monitoring of individual rooms in hotels, dormitories, hospitals and apartment buildings where a VRF/VRV or multi-split system is used as the air conditioning system. A refrigerant leak in such an installation could easily flood a room with a high concentration of refrigerant causing oxygen depletion at the floor level. For a less intrusive installation, the sensor can be remotely mounted from the main monitor.

If a pre-set alarm threshold is exceeded in an area, the IAM-100’s integrated audible and visual alarms are activated to alert occupants of the hazard. The two on-board relays can shut-off refrigerant supply lines, activate exhaust fans, or notify a building BMS or BAS systems. The IAM-100 can function as a standalone monitor or up to 16 units can be connected to an IAM Controller, which in turn can build a pyramid type monitoring system.

 

Type

Area monitor using semiconductor sensors

Gases

Refrigerants:

HFCs, HCFCs

Remote Sensor

Up to 32 ft (10 m)

Measuring Range*

typically 0 to 1,000 / 10,000 ppm

Power Supply

110 VAC, 60 Hz or 220 VAC, 50 Hz; 11 W

Status Indicators

Green and Red LEDs

Audible Alarm

85 dB buzzer (with onboard mute button)

Relay

2 redundant alarm relays, SPDT

Rating 1 A @ 24 VDC, resistive load

Alarm delay 0, 1, 5, or 10 minutes (user-selectable)

Ambient Conditions

Temperature

- 4 to +122 °F (- 20 to +50 °C)

Humidity

0 to 95 %RH, non condensing

Altitude

0 to 10,000 ft (0 to 3,050 m)

Enclosure

Powder-coated Aluminum; IP30

Size (w x h x d)

Approx. 5.8” x 3.5” x 2.5” (150 x 90 x 65 mm)

Weight

Approx. 22 oz (640 g)

Approvals

CE Mark, UL / CSA/   IEC / EN 61010-1

* See datasheet for details